Control and protection panel for 2 single-phase/three-phase pumps V2B TOSACNO | ADAJUSA
Control and protection panel for 2 single-phase/three-phase pumps V2B TOSACNO | ADAJUSA

Control panel V2B for 2 single-phase/three-phase pumps with float control - TOSCANO

€539.96 Tax included

€446.25 tax excl.

Compact control and protection panel for 2 single-phase or three-phase pumps up to 12A with automatic alternation between them by means of buoys, 230/400Vac power supply (selectable). Overload adjustment, pump anti-seizure system, phase loss protection, high level control by floats, pump temperature protection by Klixon input, alarm output by voltage free contact independent of high level and alarm general. 


Reference: V2B




Representative image for illustrative purposes, the supplied article will correspond to the indicated specifications.   

No queries yet, leave the first!
 
Compact control and protection panel for 2 single-phase or three-phase pumps up to 12A with automatic alternation between them by means of buoys, selectable 230Vac or 400Vac power supply. By means of two built-in relays, it allows the manual adjustment of the maximum intensity for the protection of each of the pumps against overload, as well as protection for lack of phase (three-phase pumps), anti-seizure system, level control by means of floats, protection of pump temperature by Klixon input (stop due to excessive heating), high level alarm siren, high level independent voltage-free contact alarm output and general alarm.


The panel has a panel on the front with function or alarm indicator lights (supply voltage to the panel, pump running, pump failure alarm, high level alarm), as well as buttons for the start and stop of the pumps and a reset button that allows the unit to be reset after an overload alarm. It has an on-load cut-off switch for forced stopping that stops the motor and does not allow it to start under any circumstances, and an operation selector located on the back of the equipment cover that has two positions for simultaneous stopping. or for the deferred stoppage of the pumps.

Automatic operation of the pumps according to the established controls and protections or manual operation that causes the forced operation of the pumps, while the thermal protections of the pumps remain active. The forced stop mode stops the motor and does not allow it to start under any circumstances. Automatic switching of the pumps due to failure, thermal failure or deactivation of one of them, so that if any incident occurs in the maintenance pump, the other pump will take over. The unit offers two voltage-free contacts, one for signaling or activating alarms due to thermal jump or high level and another contact for siren due to high level that is activated at the same time as the siren of the unit itself.

It allows the thermal protection of the pump so that in case of overload or failure of any of the phases, the thermal jump of the same occurs 7 seconds after detecting the anomaly, as well as protection against anti-seizure of the pumps so that when are in automatic state, the equipment applies one second of power every 23 hours of inactivity, to avoid seizing and deterioration in long periods of rest.


If the motor has a Klixon thermal contact, it can be connected to the terminals included in the control panel so that in the event of excessive heating of the motor, the equipment causes its shutdown due to thermal failure.


Functioning:



The high level alarm buoy will activate the pump in the event of a defect in the rest of the buoys. Likewise, the failure of any buoy enables its immediate superior.


Characteristic:

  • Manufacturer: Toscano
  • Reference: V2B
  • Control and protection of two pumps with automatic alternation by buoys
  • Dual voltage 230/400Vac
  • Automatic switching of the pumps in case of failure or deactivation of one of them.
  • Electronic overload relay adjustable from 0 to 13A (per pump)
  • Phase loss protection
  • Pump anti-seize system
  • High level alarm siren
  • General load break switch
  • Disconnector with calibrated circuit breakers
  • power contactors
  • Safety system for buoy failure
  • MAN-0-AUT buttons for automatic operation (according to the established controls and protections) or manual pump operation (forced pump start, with the overload and underload protections remaining active) and stop (stops the motor and does not allow it to run). start under any circumstances)
  • Pilot lights for voltage, high level, running and pump overload
  • Overload alarm reset button (RESET)
  • Control output for external siren.
  • High level and pump alarm contact output
  • Inputs for motor klixon thermocontact (only for 4-buoy model)
  • All control elements at 12/24 V for greater safety
  • High protection cable glands



Technical characteristics:

  • Power supply: 230/400 VAC (selectable) – 50/60Hz
  • Allowable voltage variation: +10% - 15%
  • Maximum current: 12A (per pump) AC3
  • Overload setting: 0 - 13A
  • Underload setting:
  • Buoy voltage: 12/24V
  • High level alarm output connection: NO contact
  • Input connection (power): Direct to switch
  • Output connection (motor): Direct to contactor 4 mm2
  • Fixation: Mural by clamping forks or claws
  • Working temperature: -10 +55ºC
  • Degree of protection: IP56
  • Measurements: 220 x 300 x 120mm
  • Weight: 3.5kg



Connection:









For more information, you can download the technical sheet by clicking on the "Attached Files" tab.

Material for professional use, install in compliance with the regulations in force at the place of installation.

Questions